PTC Heater HG 140

  • Pressure clamp connectors
  • Dynamic heating up
  • Wide voltage range
  • Temperature limiting
  • Energy saving
  • Clip fixing
  • Quick installation
These heaters are used in enclosures where damage from condensation must be prevented, or where the temperature may not fall below a minimum value. The aluminium profile heater body design has a chimney effect and distributes the heat evenly. The pressure clamp connectors save time and simplify installation.

Technical Data

Operating voltage 120-240V AC/DC* (min. 110V, max. 265V)
Heating element PTC resistor, self regulating and temperature limiting
Heater body extruded aluminium profile, anodised
Connection 3 pressure clamps for stranded wire 0.5-1.5mm² (with wire end ferrule) and rigid wire 0.5- 2.5mm²
Connection casing plastic according to UL94 V-0, black
Mounting clip for 35mm DIN rail, EN 50022
Fitting position vertical
Operating/Storage temperature -45 to +70 °C (-49 to +158 °F)
Protection type/Protection class IP20 / I (earthed)
Approvals VDE + UL File No. E150057
Accessoires screw fixing, Art. No. 09024.0-00 (1 packing unit = 2 pieces)

*Operating with voltages below 140V AC/DC reduces heating performance by approx. 10%.


Part No. Power* Max. current** Length Weight
14000.0-00 15W 1.5A 2.6"/65mm 0.66 lbs (0.3 kg)
14001.0-00 30W 3.0A 2.6"/65mm 0.66 lbs (0.3 kg)
14003.0-00 45W 3.5A 2.6"/65mm 0.66 lbs (0.3 kg)
14005.0-00 60W 2.5A 5.5"/140mm 1.10 lbs (0.5 kg)
14006.0-00 75W 4.0A 5.5"/140mm 1.10 lbs (0.5 kg)
14007.0-00 100W 4.5A 5.5"/140mm 1.10 lbs (0.5 kg)
14008.0-00 150W 9.0A 8.7"/220mm 1.76 lbs (0.8 kg)

*at 68°F (20°C) ambient temperature
**Inrush current

Dimensioned Drawing


Small PTC Heater HGK 047

  • Dynamic heating up
  • Energy saving
  • Wide voltage range
  • Temperature limting
  • Clip fixing
The heaters are used in enclosures where condensation is to be prevented or the temperature may not fall below a minimum value. In this way corrosion is avoided and an even temperature is ensured.

Technical Data

Heating element PTC resistor, self regulating and temperature limiting
Heater body extruded aluminium profile, anodised
Mounting clip for 35mm DIN rail, EN 50022
Fitting position vertical
Operating/Storage temperature -45 to +70 °C (-49 to +158 °F)
Protection type/Protection class IP54 / I (earthed)
Accessoires screw fixing, Art. No. 09024.0-00 (1 packing unit = 2 pieces)

Part. No.

Operating voltage
Heating capacity*
Inrush current max.
Length (L)
Weight
Connection
Approvals

04700.0-00

110-240V AC/DC** 10W 1.0A 50mm 0.10kg 3 x 0,5mm² x 300mm
sheathed cable (silicone)
VDE

04701.0-00

110-240V AC/DC** 20W 2.5A 60mm 0.20kg 3 x 0,5mm² x 300mm
sheathed cable (silicone)
VDE

04702.0-00

110-240V AC/DC** 30W 3.0A 70mm 0.20kg 3 x 0,5mm² x 300mm
sheathed cable (silicone)
VDE

04700.9-00

110-120 V AC/DC 10W 1.0A 50mm 0.10kg 3 x AWG 20 x 300mm sheathed cable UL File No. E150057

04701.9-00

110-120 V AC/DC 20W 1.5A 70mm 0.20kg 3 x AWG 20 x 300mm sheathed cable UL File No. E150057

04702.9-00

110-120 V AC/DC 30W 1.5A 100mm 0.20kg 3 x AWG 20 x 300mm sheathed cable UL File No. E150057

*at 20°C ( 68°F) ambient temperature
**(min. 110V, max 265V) Operating with voltages below 140V AC/DC reduces heating performance by approx. 10%.

Dimensioned Drawing


Compact Fan Heater HGL 046

  • Compact Design
  • Clip fixing
  • Long service life
  • Maintenance free
  • Temperature safety cut-out
Compact fan heater prevents formation of condensation. The integrated high performance axial fan provides forced air circulation and so guarantees an even temperature in enclosures. With internal terminal connector.

Technical Data

Heating element resistance heater
Temperature safety cut-out to protect against overheating in case of fan failure
Heater body anodised extruded aluminium profile
Surface temperature max. 75°C (400W)
Axial fan, ball bearing Airflow, free flow
AC: 45m³/h (50HZ) or 54m³/h (60Hz)
DC: 54m³/h
service life 50 000h at 25°C (77°F)
Connection internal connection terminal 1.5mm² with clamping torque 0.8Nm max.
Connection casing plastic according to UL94 V-0,black
Mounting clip for 35mm DIN rail, EN 50022
Fitting position vertical
Operating/Storage temperature -45 to +70 °C (-49 to +158 °F)
Protection type/Protection class IP20 / I (earthed)

Note: In the case of 24VDC and 48VDC the fan heater has to be switched via a relay. For this purpose we recommend our electronic relay SM 010 (Art. No. 01000.0-00 and 01001.0-00).


Part No. Operating voltage Heating capacity Length (L) Weight (approx.) Approvals
04640.0-00 230VAC, 50/60Hz 250W 182mm 1.10kg VDE + UL File No. E150057
04641.0-00 230VAC, 50/60Hz 400W 222mm 1.40kg VDE + UL File No. E150057
04640.9-00 120VAC, 50/60Hz 250W 182mm 1.10kg VDE + UL File No. E150057
04641.9-00 120VAC, 50/60Hz 400W 222mm 1.40kg VDE + UL File No. E150057
04640.1-00 24VDC 250W 182mm 1.10kg -
04640.2-00 48VDC 250W 182mm 1.10kg -
04641.2-00 48VDC 400W 222mm 1.40kg -

Dimensioned Drawing


PTC Fan Heater CR 027

  • Compact fan heater in PTC technology
         - Maintains minimum operating temperatures in enclosures
        - Helps to prevent failure of electronic components caused by condensation and corrosion
  • Heating power adjusts to ambient temperature
  • Integrated adjustable thermostat and control light
  • DIN rail mountable
Applications:
    Electrical & Electronic enclosures
    Telecommunications systems
    Automatic teller machines (ATM's)
    Access & Parking control systems
    Display Panels
    Personnel booths
    Ticket dispensers

Technical Data

Heating element PTC resistor, self regulating and temperature limiting
Temperature safety cut-out to protect against overheating in case of fan failure
Axial fan, ball bearing Airflow see table
service life 50 000h at 25°C (77°F)
Casing plastic according to UL94 V-0, light grey
Optical indicator thermostat control lamp
Connection 2-pole clamp 2.5mm², clamping torque 0.8Nm max.
Mounting clip for 35mm DIN rail, EN 50022
Fitting position vertical
Operating/Storage temperature 0 to +60 °C (-32 to +140 °F) / -45 to +70 °C (-49 to +158 °F)
Dimensions 100 x 128 x 165mm
Protection type/Protection class IP20 / II (double insulated)
Approvals UL File No. E204590

Art. No.
Voltage
(50Hz)*
(60Hz)*
Max. current (inrush)
Axial Fan (ball bearing)
Temperature Range
Weight
02700.0-00 220-240VAC, 50/60Hz 475W 550W 11.0A 35m³/h 0 to +60°C 0.90kg
02701.0-00 220-240VAC, 50/60Hz 550W 650W 13.0A 45m³/h 0 to +60°C 1.10kg
02700.9-00 100-120VAC, 50/60Hz 400W 550W 14.0A 35m³/h +32 to +140°F 0.90kg
02701.9-00 100-120VAC, 50/60Hz 510W 650W 15.0A 45m³/h +32 to +140°F 1.10kg

*at 68°F (20°C) ambient temperature. Also, power will vary when frequency other than listed is applied.

Dimensioned Drawing


Regulator and Monitoring

Small, compact Thermostat KT 011

  • Large setting range
  • Small size
  • Simple to mount
  • High switching performance
Thermostat (normally closed); contact breaker for regulating heaters.

Technical Data

Switch temperature difference 7K (± 4K tolerance)
Sensor element thermostatic bimetal
Contact type snap-action contact
Contact resistance < 10mOhm
Service life > 100 000 cycles
Max. switching capacity 250VAC, 10 (2) A
120VAC, 15 (2) A
DC 30W
EMC acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Connection 2-pole terminal, clamping torque 0.5Nm max.: rigid wire 2.5mm², stranded wire (with wire end ferrule) 1.5mm²
Mounting clip for 35mm DIN rail, EN50022 (or for exit filter EF 118 Series)
Casing plastic according to UL94 V-0, light grey
Dimensions 60 x 33 x 43mm
Weight approx. 40g
Fitting position variable
Operating/Storage temperature -20 to +80°C (-4 to +176°F) / -45 to +80°C (-49 to +176°F)
Protection type IP20

Setting range Art. No. Contact breaker (NC) Approvals
0 to +60°C 01140.0-00 VDE
-10 to +50°C 01142.0-00 VDE
+20 to +80°C 01159.0-00 VDE
+32 to +140°F 01140.9-00 UL File No. E164102
+14 to +122°F 01142.9-00 UL File No. E164102
0 to +60°C 01146.9-00 UL File No. E164102

Dimensioned Drawing


Small, compact Thermostat KT 011

  • Large setting range
  • Small size
  • Simple to mount
  • High switching performance
Thermostat (normally open); contact maker for regulating of filter fans and heat exchangers or for switching signal devised when temperature limit has been exceeded.

Technical Data

Switch temperature difference 7K (± 4K tolerance)
Sensor element thermostatic bimetal
Contact type snap-action contact
Contact resistance < 10mOhm
Service life > 100 000 cycles
Max. switching capacity 250VAC, 10 (2) A
120VAC, 15 (2) A
DC 30W
EMC acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Connection 2-pole terminal, clamping torque 0.5Nm max.: rigid wire 2.5mm², stranded wire (with wire end ferrule) 1.5mm²
Mounting clip for 35mm DIN rail, EN50022 (or for exit filter EF 118 Series)
Casing plastic according to UL94 V-0, light grey
Dimensions 60 x 33 x 43mm
Weight approx. 40g
Fitting position variable
Operating/Storage temperature -20 to +80°C (-4 to +176°F) / -45 to +80°C (-49 to +176°F)
Protection type IP20

Setting range Art. No. Contact maker (NO) Approvals
0 to +60°C 01141.0-00 VDE
-10 to +50°C 01143.0-00 VDE
+20 to +80°C 01158.0-00 VDE
+32 to +140°F 01141.9-00 UL File No. E164102
+14 to +122°F 01143.9-00 UL File No. E164102
0 to +60°C 01147.9-00 UL File No. E164102

Dimensioned Drawing


Dual Thermostat ZR 011

  • Two thermostats in one unit
         - one Normally Closed (NC) & one Normally Open (NO)
         - or two Normally Open (NO)
  • Each with wide adjustable temperature range
  • Available with °F or °C scale
  • DIN rail mountable
The ZR 011 houses two separate thermostats, allowing the independent control of heating and cooling or other equipment. Both thermostats offer wide adjustment ranges and are color coded for easy function recognition.

Technical Data

Sensor element Thermostatic bi-metal
Maximum tolerance +/- 7.2°F (4K)
Switching difference (hysteresis) 12.6°F +/- 5.4°F (7°C +/- 4K)
Switching capacity (max. load) NC: 10A resistive/2A inductive @ 250VAC
NO: 5A resistive/2A inductive @ 250VAC
DC 30W
Minimum load 20 mA (all voltages)
EMI/EMC compliance EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Connections 4-pole terminal for AWG 14 max. (2.5 mm²)
Mounting Clip for 35mm DIN rail (EN50022)
Dimensions (H x W x D) 2.6 x 2.0 x 1.8" (67 x 50 x 46 mm)
Housing Plastic, UL 94V-0
Weight 3.2 oz (90 g)
Protection type IP20
Operating temperature -4 to 476°F (-20 to 80°C)
Storage temperature -49 to 158 °F (-45 °C to 70 °C)
Agency approvals UL, CSA

Part No. Setting range NC Setting range NO Setting range NO
01172.0-01 32 to 140 °F 32 to 140 °F -
01175.0-01 14 to 122 °F 68 to 176 °F -
01172.0-00 0 to 60 °C 0 to 60 °C -
01175.0-00 -10 to 50 °C 20 to 80 °C -
01176.0-00 - 0 to 60 °C 0 to 60 °C
01176.0-01 - 32 to 140 °F 32 to 140 °F

Dimensioned Drawing


24 VDC + 48 VDC Electronic Relay SM 010

  • High DC switching capacity
  • Variety of applications
  • Compact design
  • Simple connection
  • Clip fixing
Electronic relay for switching DC appliances with high switching capacity. A separate conventional switch contact is used as controller (e.g. temperature regulator, humidity regulator). The electronic relay is available in 24VDC and 48VDC versions.

Technical Data

Contact type contact maker (Relay/MOSFET)
Contact resistance < 10mOhm
Service life > 100 000 cycles
EMC acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Connection 6-pole terminal, clamping torque 0.5Nm max., rigid wire 2.5mm²
Mounting clip for 35mm DIN rail, EN50022
Casing plastic according to UL94 V-0, light grey
Dimensions 67 x 50 x 46mm
Weight approx. 85g
Fitting position variable
Operating/Storage temperature -45 to +70°C (-49 to +158°F)
Protection type IP20
Approvals VDE intended

Art. No. Operating voltage Max. switching capacity
01001.0-00 24VDC (20-28VDC) 28VDC 16A
01000.0-00 48VDC (38-56VDC) 56VDC 16A

Dimensioned Drawing


FT 011 Tamperproof Thermostat

  • Compact design
  • Fixed setpoints
  • Color coded modules
  • DIN rail mountable
FTO 011NC / opens on temperature rise (redmodule housing) - for regulating heaters or for switchingsignal devices when temperature has fallen below the minimum value.

FTS 011NO / closes on temperature rise (bluemodule housing) - for regulating filter fans, heat exchang-ers, cooling devices or for switching signal devices when temperature limit has been exceeded.

Technical Data

Sensor element thermostatic bimetal
Contact type snap-action contact
Contact resistance < 20mΩ
Service life > 100 000 cycles
Max. switching capacity 10A resistive/ 2A inductive @ 120VAC
5A resistive/ 1.6A inductive @ 240VAC
DC 30W
Max. inrush current AC 10A
EMC acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Connection 2-pole terminal for AWG 14 max.(2.5mm2), torque 0.8Nm max
Housing plastic, UL 94V-0, light grey
Mounting clip for 35mm DIN rail, EN60 715
Mounting position vertical
Operating temperature -4 to +176°F(-20 to +80℃)
Storage temperature -49 to +176°F(-45 to +80℃)
Dimensions 1.85 x 1.3 x 1.3" (47x33x33mm)
Weight approx. 23g
Protection type IP20

Part No. Contact Switch-off temperature Switch-on temperature
01160.0-00 NC - open on rise 59°F / 15°C (± 9°F / 5K tolerance) 41°F / 5°C (± 9°F / 5K tolerance)
01160.0-01 NC - open on rise 77°F / 25°C (± 9°F / 5K tolerance) 59°F / 15°C (± 9°F / 5K tolerance)
    Switch-on temperature Switch-off temperature
01161.0-00 NO - close on rise 122°F / 50°C (± 11°F / 6K tolerance) 104°F / 40°C (± 12.6°F / 7K tolerance)
01161.0-01 NO - close on rise 140°F / 60°C (± 11°F / 6K tolerance) 122°F / 50°C (± 12.6°F / 7K tolerance)
01161.0-02 NO - close on rise 95°F / 35°C (± 11°F / 6K tolerance) 77°F / 25°C (± 12.6°F / 7K tolerance)

Dimensioned Drawing


Inner temperature controller for switchgear cabinet

  • Especially used for controlling fan filter, heater and heat exchanger, also could be monitoring the electric cabinet inner temperature when working as signal arouser.

Technical Data


Part No. Rated voltage
JWF6011 230/115/60/48/24V AC
60/48/24V DC

DC 24 V Electronic Thermostat ET 011

  • High DC breaking capacity
  • Low hysteresis
  • Adjustable temperature
  • Change-over contact
  • Clip fixing
Electronic thermostat for regulating high performance DC 24V equipment. Heating or cooling appliances as well as signal devices can be switched via the potential free change-over contact. In comparison to mechanical thermostats, the ET 011 has a low hysteresis making the switching point and setting accuracy more precise.

Technical Data

Switch temperature difference approx. 3K
Sensor element PTC
Contact type change-over
Contact resistance < 10mOhm
Service life > 100 000 cycles
Max. switching capacity 28VDC, 16A
EMC acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Connection 5-pole terminal, clamping torque 0.5Nm max.: rigid wire 2.5mm², stranded wire (with wire end ferrule) 1.5mm²
Mounting clip for 35mm DIN rail, EN 50022
Casing plastic according to UL94 V-0, light grey
Dimensions 67 x 50 x 46mm
Weight approx. 80g
Fitting position vertical
Operating/Storage temperature 0 to +60°C (+32 to +140°F) / -45 to +80°C (-49 to +176°F)
Protection type IP20
Approvals -

Part No. Operating voltage Setting range
01190.0-00 24VDC (20-28VDC) 0 to +60°C

Dimensioned Drawing


Mechanical Thermostat FZK 011

  • Adjustable temperature
  • High switching capacity
  • Small hysteresis
  • Terminals easily accessible
  • Clip fixing
  • Change-over contact
The mechanical thermostat is used for controlling heating and cooling equipment, filter fans or signal devices. The thermostat registers the surrounding air and can switch both inductive and resistive loads via snap-action contact.

Technical Data

Switch temperature difference 4K (± 1.5K tolerance)*
Sensor element thermostatic bimetal
Contact type change-over snap-action contact
Contact resistance < 10mOhm
Service life > 100 000 cycles
Max. switching capacity, NC 250VAC, 10 (4) A
DC 30W
Max. switching capacity, NO 250VAC, 5 (2) A
DC 30W
EMC acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Connection 4-pole terminal, clamping torque 0.5Nm max.: rigid wire 2.5mm², stranded wire (with wire end ferrule) 1.5mm²
Mounting clip for 35mm DIN rail, EN50022
Casing plastic according to UL94 V-0, light grey
Dimensions 67 x 50 x 38mm
Weight approx. 0.10kg
Fitting position variable
Operating/Storage temperature -20 to +80°C (-4 to +176°F) / -45 to +80°C (-49 to +176°F)
Protection type IP20
Approvals -
*Connecting terminal "N" (RF heating resistor) causes the thermal feedback to work and so reduces the switch temperature difference to approx. 0.5K.

Art. No. Operating voltage* Setting range
01170.0-00 230VAC +5 to +60°C
01170.0-02 230VAC -20 to +30°C

* operating voltage 120VAC wit setting °F upon request

Dimensioned Drawing


Mechanical Hygrostat MFR 012

  • Adjustable relative humidity
  • Change-over contact
  • High switching capacity
  • Easily accessible terminals
  • Clip fixing
The electromechanical hygrostat MRF 012 is designed to control enclosure heaters so that the dew point is raised when a critical relative humidity of 65% is exceeded. In this way condensation and corrosion is effectively prevented.

Technical Data

Switch difference* 4% RH (±3% tolerance)
Permissible air velocity 15m/sec
Contact type change-over contact
Contact resistance < 10mOhm
Service life > 100 000 cycles
Min. switching capacity 20V AC/DC 100 mA
Max. switching capacity 250 VAC, 5 (1) A
DC 20W
EMC acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Connection 3-pole terminal for 2.5mm², clamping torque 0.5Nm max.: rigid wire 2.5mm², stranded wire (with wire end ferrule) 1.5mm²
Mounting clip for 35mm DIN rail, EN50022
Casing plastic according to UL94 V-0, light grey
Dimensions 67 x 50 x 38mm
Weight approx. 60g
Fitting position variable
Operarting/Storage temperature 0 to +60°C (+32 to +140°F) / -20 to +80°C (-4 to +176°F)
Protection type IP20
Approvals VDE and UL submitted

*at 50% RH


Art. No. Setting range
01220.0-00 35 to 95% RH

Dimensioned Drawing


Room Thermostat

WH611

Features

Parameter

Scope of Control Applications


NTL-1000

Describing:

NTL1000 Cs is switch type breeze valve controller, apply in the control of the piping machine breeze tube breeze valve, make environment temperature in the place controled settle for set temperature.Temperature enactment. pulling out dish to point needle should set to settle temperature position for the needed.
Pull out to move a switch difference for:power switch;(open the ON - pass OFF)Circulate a mode switch.(the warm air HEAT - cold air COOL)

Characteristics:

+ The annoys a film box a feeling component.
+ Pull out dish greatly+pull out to move a switch, operate Chien clear.
+ Nicety spreading to move machine structure can protect a longevity life a work.
+86 standards install a dark box(60 mms), installing convenience.

Notice:

Inside place a temperature repair component, if have no zero lines(N) to connect to carry son on the 2nd, control influence accuracy.

NTL-3000

Features:

Technical Parameters: The main functions and features:

installation:


NTL-6000

Elegant European design
Can be mounted in combination with various types of light switches

Thermostat with setback mode type NTL-6000

Technical Data

Supply voltage 230V +10/-15%, 50/60 Hz
Output relay SPST - type NTL-6000 16A, max. 3600W
14A, max. 3200W
Built-in interrupter 1-pole
Temperature range +5/+40°C
Setback mode (via remote timer) 5°C
On/off differential 0.4°C
Ambient temperature 0/+50°C
Housing
- type NTL-6000
IP 20
IP 21
Sensor type - heating is switched off in case of sensor failure NTC
Dimensions (H/W/D) 80/80/50 mm

NTL-2000

It can be used to the indoor temperature controlling of hotel.and home family with the features of novel outline and simple in stnxture,designed reliable and easy to install.
Contact capacity:6A/220V~50HZ
Operating range:10''''''''C~30''''''''C
Temperature sense
Component:Air-charged film case
Appendix:air speed gear,gear shifting
on temperature alternation

Yueqing Langir Electric Co.,Ltd. | SunShine Electric. Co.,LTD. Tel: 86-577-62737672 Mobile: 86-13706605914 Fax: 86-577-62737671 E-mail: sunshine@sunshinele.com